0. - Product families:

EVC, EVF, WALL


1. - Earthling Connections diagrams:

The IT system is not recommended for Charging Stations installation, if you use this system it requires the creation of a separate TN-S network for charging infrastructure.

The voltage between Neutral (N) and Ground (PE) must be below 10 V.

The Ground resistance must comply with current regulations and, in any case, be less than 100 Ohms.


2. - Individualized Supply Circuit:

The supply of each Charging Point is performed using an individualized circuit.

The electric vehicles charging network should not be affected by the failure of other circuits or other changing stations.


3. – Overcurrent protection:

Each individual line must be protected by:

  • A single phase circuit breaker 20 A curve C for normal charges ;
  • A three phase circuit breaker 20 A curve C for medium charges until 11kVA;
  • A three phase circuit breaker 40 A curve C for charges until 22 kVA.

Note*: Generally, the ENSTO Charging Points are provided with MCB of 16A and /or 32A


4. - Protection against direct contact:

Each Charging Point must be protected individually by a differential-residual current protection device (RCD) at most equal to 300 mA *, respecting the selectivity of the specific electrical installation.

RCD protecting must comply with local current regulations. ENSTO recommend the following:

  • Type A RCD in single phase.
  • Type B RCD in three phases.

 

Note*: The ENSTO Charging Points have a RCD with a sensitivity of 30mA.


5. - Charging Station electrical connections:

The Ensto Charging Stations are provided with connection terminals for the three phases (L1, L2, L3) Neutral (N) and Ground (PE).

In the case of the electrical system does not allow a connection with three phases (380V), the Charging Station can be connected in single phase (230V) using the connection terminals: L1, N and PE.

In all installation cases, single phase or three phase, it is recommended to perform a phase rotation on the charging station network.

Note: In a single phase installation, do not link terminals L1, L2, L3 between them.


6. -Ensto Charging Points Maximum Power:

Each Charging point can be connected to the electric network using a single phase or three phase. This provides the flexibility of 2 different levels of maximum power:

  • Single phase:    230V, 32A        Total: 7.3 kW
  • Three phase:     380V, 32A        Total: 22 kW

7. - Charging Station Installation:

Depending on the Body or accessory you purchase, the Ensto Charging Station can be installed:

On Wall: When selecting the installation location, ensure that the wall is made from a suitable and robust material. The mounting surface must be flat and vertical.

On Ground: On existing concrete surface with sufficient size to answer the product needs. Or, make a concrete block.  In both cases M8 threaded rods or M8 expandable bolt will be needed to attach the charging station.

In 2 cases it is recommended to take steps to prevent the nuts / bolts loosen over time.

Note 1: In all cases electric cable routing must be taken into account when planning the installation. See product Installation instructions for details.

Note 2: To facilitate the work, installation accessories are available. More details in each product installation instructions.


8. – Power Cable:

The cable section must be verified before installation. Consider: supplier's specifications, type of cable, installation mode, installation type, length, and other factors.


Example: Single phase cable (220 volts with a cosj 1). The lengths are expressed in meters, with a consistent voltage drop of 3%.

KW

A

Gauge in mm²

1,5

2,5

4

6

10

16

25

35

50

70

95

120

150

185

240

0,5

2,3

100

165

265

395












1

4,6

50

84

135

200

335

530










1,5

6,8

33

57

90

130

225

355

565









2

9

25

43

68

100

170

265

430

595








2,5

11,5

20

34

54

80

135

210

340

470

630







3

13,5

17

29

45

66

110

180

285

395

520







3,5

16

14

24

39

56

96

155

245

335

450







4

18


21

34

49

84

135

210

295

395

580






4,5

20


19

30

44

75

120

190

260

350

515






5

23



27

39

68

105

170

235

315

460

630





6

27



23

32

56

90

140

195

260

385

530





7

32




28

48

76

120

170

225

330

460

570




8

36





42

67

105

145

195

290

400

500

620



9

41





38

60

94

130

175

255

355

440

550



10

45





34

54

84

120

155

230

320

400

495

615


12

55






45

70

98

130

190

265

330

410

510


14

64






38

60

84

110

165

230

285

350

435

560

16

73







53

74

99

145

200

250

305

380

500

18

82







47

65

88

125

175

220

270

340

440

20

91








59

79

115

160

200

245

310

400

25

114









64

98

130

150

195

245

315

30

136










77

105

135

165

205

265

35

159

 

 

 

 

 

 

 

 

 

 

90

115

140

175

225

40

182











80

100

125

155

200

45

205












89

110

135

175

50

227













98

120

160

 

Example: Three phase cable (380 volts AC with a cos j 0.8). The lengths are expressed in meters, with a consistent voltage drop of 5%.

KW

A

Gauge in mm²

1,5

2,5

4

6

10

16

25

35

50

70

95

120

150

185

240

2,5

5

190

325

510

745












3

6

160

270

420

620

3,5

7

135

230

365

540

895

4

8

120

200

320

470

785

4,5

9

105

180

285

420

700

5

10

96

165

255

375

630

970

6

12

79

135

210

315

525

810

7

14

68

115

180

270

455

700

8

16

60

105

160

240

400

610

940

9

18

51

92

145

215

355

550

850

10

19


84

130

190

320

500

780

12

23

69

110

160

265

415

640

880

14

27


94

140

230

355

550

750

16

31

81

120

200

315

485

655

860

18

35


110

180

280

430

580

770

20

38

98

160

255

390

520

690

25

48


130

205

315

420

555

760

30

57


170

260

355

465

640

840

35

67

145

225

300

400

550

730

40

76


195

260

350

480

640

745

45

86

175

235

310

430

565

670

770

50

95

160

215

285

385

510

600

695

60

114


180

235

320

420

500

580

680

70

133

Heating limit

200

275

365

430

495

580

80

152









240

315

375

430

510

600

90

171

215

280

355

385

445

535

100

190


250

300

350

405

480

120

228


250

290

340

400

140

266


250

290

345

 

9. - Mechanical Protection:

To prolong the life of the Charging Station, Ensto recommends installing a flexible or rigid mechanical protection.                           



                   

                           Example A                                                                        Example B


10. - Commissioning:

For each charging point we need check:

  • Ground resistance. (must be less than 100 ohms)
  • Voltage between Ground and Neutral (must be less than 10 volts)
  • Voltage between Neutral and each phase.
  • Voltage between each phase (L1 and L2, L1 and L3, L2 and L3)

All these tests can be performed from electrical main terminals of each Charging point and the results must comply with local regulations.


Note: In order to test the electrical circuit of each charging point (from charging station main terminals to charging socket) a specific tool is available and sold separately.

 

 

  • No labels